Time Delay Relay Module

 


Top view


Side View



Click here for additional details and specification

Key Features

Increases load-handling ability of flow monitor/switches

 

Features

DPDT 10 Amp Contacts

12 VDC Control Circuit

LED Status Light

Adjustable Time Delay

120 VAC Power 

Applications

Contactors

Motors

Solenoid Coils

Invert Switch State

Filter Pulsating Flow Signals 

Operation

With 120 VAC supplied, the flow monitor’s contacts are connected to the 12VDC 10 mA control circuit provided by the relay.  When the flow monitor contacts are closed for a period of time the relay contacts are then energized.  This period of time can be adjusted from 50 milliseconds to 5.0 seconds.  A LED light gives the status of the control circuit.

Specifications

Supply Voltage: 120VAC
Control Circuit: 12 VDC 10 mA max.

Output Contacts: Double pole double throw isolated, 

rated at 10A 250 VAC resistive

Temperature Range: -40 to 185° F (-40 to 85° C)

Life Expectancy: 20 million operations with no load, 

100,000 operations at maximum rating.

Physical Data

Mounting: Two #6 screws (.175” dia. Holes)

Terminals: .25” quick (spade) connects 

 


Kalrez® and Viton® are registered trademarks of DuPont Dow Elastomers..
Teflon® is a registered trademark of E. I. du Pont de Nemours and Company.

 

Home - About - Products - Distributors - Contact

© CTE Chem Tec -
Designed and Hosted by ABC Web Service